Voice Evacuation Intelligibility Helper

A voice evacuation system that is loud but unintelligible fails its purpose and, increasingly, its acceptance test. This tool covers the three questions a designer and an inspector ask: do the measured STI values in each space pass NFPA 72-2022 Annex D, will this room's reverberation and background noise allow intelligible speech at all, and how many ceiling speakers at what tap does it take to get there.

Educational estimator, not a sealed design or a test report. Intelligibility is proven by measurement with a listed STI meter (STIPA) in the acceptance test, not by calculation. Panel 1 applies the pass criteria of NFPA 72-2022 Annex D to values you measured. Panels 2 and 3 are acoustic planning estimates using standard room-acoustics relationships β€” they are not code values and they are not a substitute for a speaker-modeling program or the field test. Texas jurisdictions adopt different code editions and some adopt stricter intelligibility thresholds β€” confirm with your AHJ.

1. Do the measured STI values pass?

NFPA 72-2022 Β§18.4.11 requires voice communications to be intelligible, and Chapter 24 applies it to each acoustically distinguishable space (ADS) where intelligibility is required. Annex D.2.4.1 gives the pass criteria: within an ADS, at least 90 % of the measurement locations have an STI of 0.45 (CIS 0.65) or better, and the average of all locations is at least STI 0.50 (CIS 0.70).

CIS = 1 + log10(STI). STI 0.45 = CIS 0.65; STI 0.50 = CIS 0.70. Most STIPA meters report both.
Use the measured value at each location (several readings averaged per location per the meter's method). Representative locations across the ADS, at listener ear height.

2. Will this room allow intelligible speech? (planning estimate)

Estimate, not code. This panel uses the Sabine reverberation equation and a simplified speech transmission index model to flag rooms where intelligibility will be hard before any speaker is hung. Hard, tall, empty spaces (gyms, atriums, parking structures) are the usual trouble.
Typical mid-frequency averages from room-acoustics practice, not code values. Enter the room empty if it will be tested empty.
What the system will deliver at ear height β€” Panel 3 estimates this from the speaker tap and height. NFPA 72 Β§18.4.4.1 needs the voice signal at least 15 dBA over average ambient for audibility; intelligibility usually wants more.

3. How many ceiling speakers, at what tap? (planning estimate)

Estimate, not code. NFPA 72 does not prescribe a speaker spacing; it prescribes the result (audible per Β§18.4.4.1, intelligible per Β§18.4.11). This panel uses coverage geometry from the speaker's dispersion angle and the standard sensitivity equation to size a layout for the designer to refine in a modeling program.
Listener ear height is taken as 5 ft (standing). Coverage is computed at that plane.
Use the βˆ’6 dB coverage angle at 2 kHz or the manufacturer's stated value. Not a code number.
Industry layout conventions. Minimum overlap keeps the βˆ’6 dB points covered on the diagonal; intelligibility designs rarely use edge-to-edge.

Related

One company. One report. One bill.

You shouldn't have to chase contractors to keep people safe.

We run every fire-protection system in your Texas building under one account. One technician team. One AHJ-ready report after each visit. One monthly bill. Start with a free 48-hour compliance audit β€” no commitment, no sales pitch, just a written answer to the question "are we compliant right now?"