Educational estimator. Not a sealed design and not a substitute for a walk-through by the fire marshal or a licensed extinguisher technician. Counts below are the code-minimum from area math per NFPA 10-2022 Table 6.2.1.1 and IFC 2021 §906; the 75-ft travel distance usually requires more units than the area math alone. Texas jurisdictions adopt different code editions and local amendments govern — confirm the adopted edition with your AHJ.
Extinguisher count and placement
Class A — per floor (NFPA 10 Table 6.2.1.1)
Class A required (all floors)
—
Travel distance check CHECKCount is the floor of the answer — walk the floor: no point may be more than 75 ft actual walking distance from an extinguisher (§6.2.1.1, Table 6.2.1.1; measured along the walking path, not straight line — NFPA 10 Annex A, definition of travel distance). Planning aid, not code: a 75-ft travel radius covers at most roughly 11,250 sf of open floor, which is why the table caps there.
75 ft max
Class B — flammable liquids (NFPA 10 Table 6.3.1.1)
Spill-fire rating and travel distance
—
Appreciable-depth tank — minimum B rating (§6.3.2)
—
Class K — commercial cooking (NFPA 10 §6.6)
Class K extinguisher required within 30 ft of each cooking hazard (deep-fat fryers, griddles, etc.)Minimum one per cooking area (§6.6.2). Where the cooking media is vegetable or animal oils and fats, Class K is required (§6.6.1).
—
Class C — energized electrical equipment (NFPA 10 §6.4)
No separate count. Where energized electrical equipment is present, the extinguishers must carry a Class C rating (the "C" on the label); size and placement follow the Class A or Class B hazard that is actually present. An ABC-rated unit satisfies this.
C rating
Mounting height (NFPA 10 §6.1.3.8)
Top of extinguisher — maximum height above floor
—
Bottom of extinguisher — minimum clearance above floorIn no case shall clearance between the bottom of a hand-portable extinguisher and the floor be less than 4 in (§6.1.3.8.3).
—
Placement and upkeep
Extinguishers must be conspicuously located, readily accessible, and along normal paths of travel, including exits (§6.1.3.1, §6.1.3.2). Where visual obstructions cannot be avoided, provide signs or other means to indicate the extinguisher location (§6.1.3.3).
Once installed: monthly visual inspection §7.2, annual maintenance by a certified person §7.3, 6-year internal examination for stored-pressure dry chemical units (§7.3.3), hydrostatic testing per Chapter 8.
Show the math
Code cited: NFPA 10-2022 §6.2.1, Table 6.2.1.1 (Class A size and placement); §6.3.1, Table 6.3.1.1 (Class B); §6.3.2 (appreciable depth); §6.6.2 (Class K); §6.1.3.8 (mounting height); IFC 2021 §906 (where required; Table 906.3(1) reproduces the NFPA 10 Class A table and §906.3 points to NFPA 10 for placement).