Portable Extinguisher Count + Placement Calculator

Too few extinguishers, the wrong class in the kitchen, or a unit hung too high are the most common write-ups on an annual fire inspection. Enter each floor's area, the hazard class, and the rating on the label — this tool applies NFPA 10-2022 Table 6.2.1.1 to compute the minimum Class A count per floor, checks Class B and Class K travel distance, and gives the mounting height for the unit weight.

Educational estimator. Not a sealed design and not a substitute for a walk-through by the fire marshal or a licensed extinguisher technician. Counts below are the code-minimum from area math per NFPA 10-2022 Table 6.2.1.1 and IFC 2021 §906; the 75-ft travel distance usually requires more units than the area math alone. Texas jurisdictions adopt different code editions and local amendments govern — confirm the adopted edition with your AHJ.

A — Class A: ordinary combustibles, by floor

NFPA 10 §5.4 examples. Light: offices, classrooms, churches, hotel guest rooms. Ordinary: mercantile, light manufacturing, parking garages, restaurant dining, auto showrooms, warehouses of non-combustible goods. Extra: woodworking, vehicle repair, aircraft servicing, flammable-liquid handling, high-piled combustible storage, upholstered furniture manufacturing. When in doubt, pick the higher hazard.
Read the rating off the UL label on the cylinder. "3-A:40-B:C" means 3 units of A, 40 units of B, rated for Class C. Common units: 5 lb ABC = 2-A or 3-A; 10 lb ABC = 4-A; 20 lb ABC = 10-A; 2.5 gal water = 2-A.
One row per floor. NFPA 10 §6.2.1.2.1 computes the count floor by floor — floors are never pooled.

B — Class B: flammable liquids and gases (optional)

Fuel storage, paint, solvents, generator rooms, vehicle service, lab chemicals. Most offices and classrooms do not need this section.

C — Class K: commercial cooking (optional)

Deep-fat fryers, griddles, ranges, woks using vegetable or animal oils and fats (NFPA 10 §6.6.1). A break-room microwave does not count.

D — Mounting height

Gross (full, charged) weight from the label or spec sheet, not the agent weight. A "10 lb ABC" typically weighs 16–18 lb gross; a "20 lb" unit typically 30–35 lb gross. Wheeled units are excluded from this height rule.