Exit Sign / Emergency Lighting Placement Calculator
A corridor where the exit sign disappears behind a soffit, a stair that goes dark at minute 60 of the annual test, a light-meter reading nobody compared to the threshold — these are the findings that fail an egress inspection. This tool applies IBC 2021 §1013 sign spacing, estimates emergency lighting units from your fixture's rated spacing, and checks meter readings against the §1008.3.5 / NFPA 101 §7.9.2.1 illumination limits.
1. Exit sign count along a corridor or exit passageway
IBC 2021 §1013.1: no point in an exit access corridor or exit passageway may be more than 100 feet, or the listed viewing distance of the sign, whichever is less, from the nearest visible exit sign. Enter the run and the tool counts the signs it takes to satisfy that rule.
Exit sign count
Assumes a sign is visible from both ends; obstructions, offsets, or soffits add signs.
Show the math
Construction and illumination reminders for every sign counted
- Group R-1 floor-level signs (§1013.2): in addition to the signs above, provide a floor-level exit sign with the bottom of the sign 10–12 inches above the floor, on the wall on the latch side of the door.
- Tactile signs (§1013.4): a raised-character and Braille EXIT sign is required at each exit door to an interior exit stairway or ramp, exit passageway, and exit discharge.
- Illuminated at all times (§1013.3): every exit sign must be internally or externally illuminated whenever the building is occupied.
- Externally illuminated signs (§1013.6.1): letters at least 6 inches high with principal strokes at least 3/4 inch wide.
- Face illumination (§1013.6.2; NFPA 101 §7.10.6.3): externally illuminated sign face at least 5 footcandles (54 lux).
- Emergency power (§1013.6.3; NFPA 101 §7.10.9): at least 90 minutes on battery or generator when normal power fails.
When NO exit sign is required — §1013.1 exceptions
Check each condition that applies to the space you are marking. If one applies, that door or room does not need a sign under the base code.
Code cited: IBC 2021 §1013.1, §1013.2, §1013.3, §1013.4, §1013.6; NFPA 101-2021 §7.10.1.5.2, §7.10.6.3 — exit sign location and spacing, floor-level signs in R-1, illumination, tactile signs, sign construction and external illumination.
2. Emergency lighting unit estimate
IBC 2021 §1008.3 lists where emergency power for egress illumination is required. The unit count below is a planning estimate from the manufacturer's rated spacing; a photometric layout by the engineer of record is still required.
Emergency lighting units
Planning estimate from the manufacturer spacing; a photometric layout is still required.
Show the math
- Duration (§1008.3.4): emergency power must run the egress illumination for at least 90 minutes — storage batteries, unit equipment, or an on-site generator installed per §2702.
- Normal-power illumination (§1008.2.1): the means of egress must be lit to at least 1 footcandle (11 lux) at the walking surface whenever the building is occupied. Exceptions exist for R-1, R-2, and R-3 dwelling and sleeping units, aisles in Group A lit to 0.2 fc during performances, and I-3 sleeping units — verify the exception before relying on it.
Inventory: where emergency lighting is required
Check off each space type present in the building. The count updates below so you know how many separate paths to run through this panel.
§1008.3.1 — rooms and spaces that require two or more exits or exit accesses
§1008.3.2 — buildings that require two or more exits
§1008.3.3 — always required, regardless of exit count
Code cited: IBC 2021 §1008.2.1, §1008.3.1–1008.3.4; NFPA 101-2021 §7.9.1 — means of egress illumination level, emergency power required locations, and 90-minute duration.
3. Emergency illumination compliance check
Take light-meter readings at the floor along the path with normal power off and the emergency units running. Paste the readings and the tool checks them against IBC 2021 §1008.3.5 and NFPA 101-2021 §7.9.2.1: average, minimum at any point, and the 40:1 uniformity ratio.
Illumination check —
Show the math
- Group I-2 (hospitals, nursing homes) — §1008.3.5: failure of a single lamp in a luminaire must not reduce illumination at any point below 0.2 fc (2.2 lux). This tool does not model single-lamp failure; check it on the photometric layout.
- Where to measure: §1008.3.5 sets these levels at the walking surface along the path of egress. Readings taken at eye level or on a wall are not comparable.
Code cited: IBC 2021 §1008.3.5; NFPA 101-2021 §7.9.2.1 — emergency illumination: 1 fc average and 0.1 fc minimum initially, 0.6 fc average and 0.06 fc minimum at the end of the duration, 40:1 maximum-to-minimum ratio.